Panel Transformer, 110V Output, 300VA - CCM300/110
Description
- Multi-tapped primary.
- Centre tapped secondary.
- Insulation between windings.
- Short duration surge load capacity.
- 50/60Hz operation.
- Varnish impregnated windings.
- Touch proof terminals.
For 110V out, connect one wire to a 55V terminal and your other wire to the remaining 55V terminal.
For centre-tap earthed (CTE) applications, ensure the 0V centre-tap is connected to earth
These transformers can also be supplied in enclosures, with ratings from IP22 to IP55.
Primary Connection Instructions
|
||
Supply Voltage
|
Connection 1
|
Connection 2
|
220V
|
-15
|
230
|
230V
|
0
|
|
240V
|
+15
|
|
380V
|
-15
|
400
|
400V
|
0
|
|
415V
|
+15
|
The CCM range of transformers replaced our CRT range of transformers. CRT type transformers may be ordered as spares however they are subject to lead times associated with built to order transformers rather than being available ex-works.
Specifications
- Weight (kg): 4.1
- Fixing Hole Accepts: M5
- Fixing Footprint (WxD mm): 90x68
- Height (mm): 120
- Depth (mm): 88
- Width (mm): 120
- Unit Drawing pdf: 3954 CCM300.pdf
- Continuous Rating: 300VA
- Input Voltage: +15V / 0V / -15V / 230V / 400V
- Output Voltages: 110V (55V-0-55V)
- Earth Tab: Faston tab 6.3x0.8mm
- Supply Tolerance: +6%, -10%
- Pri-Sec Insulation: 4.5kV
- Ambient: 40ºC Max
- Isolation Class: 1
- Insulation Class: B